7A. TROUBLESHOOTING GUIDE
SET THERMOSTAT TO CALL FOR HEAT
IS THE HEATER BURNING?
THE SYSTEM IS WORKING PROPERLY.
STOP.
YES
NO
IS THERE LINE VOLTAGE TO
THE THERMOSTAT CONTROL?
CHECK CIRCUIT BREAKERS OR FUSE
CHECK ON/OFF SWITCH
NO
YES
CONT’D
IS THERE A SPARK AT IGNITION
SPARK IGNITER?
CHECK SPARK IGNITER CERAMIC FOR
CRACK, REPLACE SPARK IGNITER IF NECES
SARY
CHECK HI-VOLTAGE WIRE C O N N E C T I O N
FROM SPARK IGNITER TO IGNITION MODULE
ENSURE HIGH VOLTAGE SPARK IS
GENERATED AT THE IGNITION CONTROL
TERMINAL BY FOLLOWING THE STEPS AS
SHOWN BELOW:
-SHUT OFF ELECTRICAL POWER
-REMOVE THE HI-VOLTAGE WIRE ON THE
IGNITION CONTROL TERMINAL
WARNING: BEFORE REMOVING HI-VOLTAGE
WIRE, ELECTRICAL POWER TO THE SYSTEM
MUST BE SHUT OFF. THIS TERMINAL CARRIES
15,000 AC VOLTS.
TURN ON ELECTRICAL POWER
PLACE A METAL CONDUCTOR 1/8" AWAY
FROM THE HI-VOLTAGE TERMINALS
WARNING: THE HANDLE ON THE METAL
CONDUCTOR MUST BE HEAVILY INSULATED.
A LONG SCREW DRIVER WITH THICK PLASTIC
INSULATION HANDLE IS IDEAL FOR THIS
APPLICATION.
IF NO SPARKING OCCURS ACROSS THE
GAP TO THE METAL CONDUCTOR, THEN
THE IGNITION CONTROL IS DEFECTIVE.
REPLACE WITH NEW IGNITION CONTROL. -
SHUT OFF ELECTRICAL POWER AND RE-
CONNECT THE HI-VOLTAGE WIRE.